| Windmill Cables | |||
| EPR/HFXLEVA LSOH 0.6/1kV Torsion Resistant Power Cable | HFEPR/HFEVA 0.6/1kV LSOH Screened Torsion Resistant Power Cable | Al Conductor EPR/XLEVA 0.6/1kV LSOH Power Cable 90℃ | more |
Windmill Cables
Indoor/Outdoor PROFIBUS
Application
Indoor/Outdoor PROFIBUS cables are used in the cell and field area, suitable for indoor or outdoor installation
and are equipped with special PVC or PE sheath.
Standards
DIN 19245 T3
EN 50170
Construction

Conductor: Bare copper 1×22AWG.
Insulation: Foam skin PE.
Cable Element: Two cores with filler.
Screen 1: Polyester tape over stranded bundle.
Screen 2: Aluminium/Polyester tape.
Overall Screen: Tinned copper braid.
Sheath: PVC/PE.
Technical Data
Operating Temperatures:-40℃~+70℃
Minimum Bending Radius:120mm
Impedance:150Ohm +/-10%
Maximum Conductor Resistance @20°C:55Ohm/km
Nominal Mutual Capacitance:35nF/km
Minimum Insulation Resistance:1GOhm×km
Attenuation @9.6kHz:<2.5dB/km
Attenuation @38.4kHz:<4dB/km
Attenuation @4kHz:<22dB/km
Attenuation @16kHz:<42dB/km
Flame Retardant:IEC 60332-1/FT 1/FT 4
UV Resistant:Yes
Dimensions and Weight
| Construction | Nominal Overall Diameter | Nominal Weight |
|---|---|---|
| No. of cores×mm | mm | kg/km |
| 1×2×0.64 (PVC Sheath) | 8.0 | 75 |
| 1×2×0.64 (PE Sheath) | 8.0 | 65 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information